HESP series hybrid inverters (single-phase 4-12 kW and three-phase 8-12 kW)

SRNE 04 error code

Battery undervoltage stop-discharge (BatLowEod): the battery has reached the low-voltage cut-off and the inverter has stopped discharging.

Likely causes

  • Battery at end of discharge after a long grid outage
  • Low-voltage cut-off set above the battery's real capability
  • Bank not recharged since the last outage
  • Heavy load pulling the voltage below cut-off

Checks to run, in order

  1. 1Measure battery voltage and read SOC from the BMS
  2. 2Compare with the [Batt. voltage low fault] and recovery values
  3. 3Confirm the battery was charging before the trip
  4. 4Check cable voltage drop under load

Fixes

  • Charge the battery above the low-voltage recovery value, then restart
  • Reduce the load or deepen the discharge reserve
  • Correct the cut-off setting to match the battery datasheet

When to escalate

If end-of-discharge repeats immediately after a full charge, arrange a battery capacity test with the distributor before changing settings.

Fix it with the right tools

Check the system around the fault before replacing parts: load, battery bank, PV string and commissioning settings. If you need a second opinion, send the code and your inverter model to our team.

Before you open the inverter

  • Isolate both the AC and DC sides, then confirm the display is dead before touching terminals.
  • Use insulated tools and one hand where possible. DC arcs do not self-extinguish like AC.
  • If you see burnt terminals, swollen cells, leaking electrolyte or a burning smell, stop and escalate instead of resetting the fault.

Questions installers ask

What does SRNE 04 mean?

Battery undervoltage stop-discharge (BatLowEod): the battery has reached the low-voltage cut-off and the inverter has stopped discharging.

How do I fix SRNE 04?

Charge the battery above the low-voltage recovery value, then restart Reduce the load or deepen the discharge reserve Correct the cut-off setting to match the battery datasheet

When should I escalate SRNE 04?

If end-of-discharge repeats immediately after a full charge, arrange a battery capacity test with the distributor before changing settings.

Can I reset SRNE 04 myself?

Only after isolating the AC and DC sides and running the checks above. If SRNE 04 returns immediately, stop resetting it and escalate; a repeating fault usually points to a real circuit, battery or hardware problem.

Which models show SRNE 04?

SRNE 04 is documented for HESP series hybrid inverters (single-phase 4-12 kW and three-phase 8-12 kW). Confirm the code on your own unit's display or manual before ordering parts.

More SRNE error codes

Guidance reviewed 17 October 2026 by the Mishka Energy installer team. Error codes vary by brand, model family and firmware; confirm against the manufacturer manual.