IVGM5-8K LP2G1 hybrid inverters (fault code list, solid fault LED)

Felicity 27 error code

Battery over-current fault: current into or out of the battery exceeded the inverter's protection limit.

Likely causes

  • Load surge drawing more current than the battery can supply
  • Battery bank too small for the inverter's output
  • Charge current set too high for the pack
  • A short or near-short on the battery circuit

Checks to run, in order

  1. 1Clamp the battery cable during charge and discharge and compare with the battery's current limits
  2. 2Check the charge current setting against the battery datasheet
  3. 3Review the connected load and any large motor or compressor starting
  4. 4Inspect battery cables and terminals for a short or loose connection

Fixes

  • Reduce the load and stagger large appliances
  • Lower the charge current to the battery's rating
  • Restart 2-3 times and retest under load

When to escalate

If the over-current trips with the load and charge current within the battery rating, escalate for inverter and battery inspection.

Fix it with the right tools

Check the system around the fault before replacing parts: load, battery bank, PV string and commissioning settings. If you need a second opinion, send the code and your inverter model to our team.

Before you open the inverter

  • Isolate both the AC and DC sides, then confirm the display is dead before touching terminals.
  • Use insulated tools and one hand where possible. DC arcs do not self-extinguish like AC.
  • If you see burnt terminals, swollen cells, leaking electrolyte or a burning smell, stop and escalate instead of resetting the fault.

Questions installers ask

What does Felicity 27 mean?

Battery over-current fault: current into or out of the battery exceeded the inverter's protection limit.

How do I fix Felicity 27?

Reduce the load and stagger large appliances Lower the charge current to the battery's rating Restart 2-3 times and retest under load

When should I escalate Felicity 27?

If the over-current trips with the load and charge current within the battery rating, escalate for inverter and battery inspection.

Can I reset Felicity 27 myself?

Only after isolating the AC and DC sides and running the checks above. If Felicity 27 returns immediately, stop resetting it and escalate; a repeating fault usually points to a real circuit, battery or hardware problem.

Which models show Felicity 27?

Felicity 27 is documented for IVGM5-8K LP2G1 hybrid inverters (fault code list, solid fault LED). Confirm the code on your own unit's display or manual before ordering parts.

More Felicity error codes

Guidance reviewed 17 October 2026 by the Mishka Energy installer team. Error codes vary by brand, model family and firmware; confirm against the manufacturer manual.