IVGM5-8K LP2G1 hybrid inverters (warning code list, flashing fault LED)

Felicity 38 error code

Grid reverse-sequence alarm: the phase order at the grid input is reversed.

Likely causes

  • Grid phases landed in the wrong order
  • Wiring changed at the main distribution board
  • Phase order altered by a generator or changeover switch
  • One phase lost, making the sequence read incorrectly

Checks to run, in order

  1. 1Measure the phase sequence at the inverter grid terminals
  2. 2Measure all phase-to-phase and phase-to-neutral voltages
  3. 3Check the phase order at the main board and changeover switch
  4. 4Compare with the installation drawing

Fixes

  • Swap two phases to correct the sequence
  • Restore any missing phase or loose connection
  • Restart and confirm the inverter synchronises

When to escalate

If the phase order is correct at the terminals and code 38 persists, escalate for input-board service.

Fix it with the right tools

Check the system around the fault before replacing parts: load, battery bank, PV string and commissioning settings. If you need a second opinion, send the code and your inverter model to our team.

Before you open the inverter

  • Isolate both the AC and DC sides, then confirm the display is dead before touching terminals.
  • Use insulated tools and one hand where possible. DC arcs do not self-extinguish like AC.
  • If you see burnt terminals, swollen cells, leaking electrolyte or a burning smell, stop and escalate instead of resetting the fault.

Questions installers ask

What does Felicity 38 mean?

Grid reverse-sequence alarm: the phase order at the grid input is reversed.

How do I fix Felicity 38?

Swap two phases to correct the sequence Restore any missing phase or loose connection Restart and confirm the inverter synchronises

When should I escalate Felicity 38?

If the phase order is correct at the terminals and code 38 persists, escalate for input-board service.

Can I reset Felicity 38 myself?

Only after isolating the AC and DC sides and running the checks above. If Felicity 38 returns immediately, stop resetting it and escalate; a repeating fault usually points to a real circuit, battery or hardware problem.

Which models show Felicity 38?

Felicity 38 is documented for IVGM5-8K LP2G1 hybrid inverters (warning code list, flashing fault LED). Confirm the code on your own unit's display or manual before ordering parts.

More Felicity error codes

Guidance reviewed 17 October 2026 by the Mishka Energy installer team. Error codes vary by brand, model family and firmware; confirm against the manufacturer manual.