IVGM5-8K LP2G1 hybrid inverters (fault code list, solid fault LED)
Felicity 41 error code
BUS over-voltage fault: the internal DC bus voltage exceeded its protection ceiling.
Likely causes
- PV or AC surge feeding the DC bus
- Internal voltage-regulation fault
- Battery voltage above the inverter's range
- Lightning damage to the input stage
Checks to run, in order
- 1Measure the PV and battery voltages against the inverter specification
- 2Restart 2-3 times and note whether the code returns under load
- 3Check for signs of a lightning strike or surge on the PV and AC side
- 4Confirm the battery bank voltage matches the inverter model
Fixes
- Correct any over-voltage source and restart
- If the bus trips again with normal input voltages, remove the unit from service
- Book service for the power stage
When to escalate
A repeated code 41 with normal PV and battery voltages is an internal bus fault - escalate to the distributor.
Fix it with the right tools
Check the system around the fault before replacing parts: load, battery bank, PV string and commissioning settings. If you need a second opinion, send the code and your inverter model to our team.
Before you open the inverter
- Isolate both the AC and DC sides, then confirm the display is dead before touching terminals.
- Use insulated tools and one hand where possible. DC arcs do not self-extinguish like AC.
- If you see burnt terminals, swollen cells, leaking electrolyte or a burning smell, stop and escalate instead of resetting the fault.
Questions installers ask
What does Felicity 41 mean?
BUS over-voltage fault: the internal DC bus voltage exceeded its protection ceiling.
How do I fix Felicity 41?
Correct any over-voltage source and restart If the bus trips again with normal input voltages, remove the unit from service Book service for the power stage
When should I escalate Felicity 41?
A repeated code 41 with normal PV and battery voltages is an internal bus fault - escalate to the distributor.
Can I reset Felicity 41 myself?
Only after isolating the AC and DC sides and running the checks above. If Felicity 41 returns immediately, stop resetting it and escalate; a repeating fault usually points to a real circuit, battery or hardware problem.
Which models show Felicity 41?
Felicity 41 is documented for IVGM5-8K LP2G1 hybrid inverters (fault code list, solid fault LED). Confirm the code on your own unit's display or manual before ordering parts.
More Felicity error codes
- Felicity 04Low cell voltage / over-discharge protection.
- Felicity 05PV over-current fault: the PV input current exceeded the inverter's PV input limit.
- Felicity 18PV short-circuit fault on the PV input; in the warning list the same number means battery under-voltage alarm.
- Felicity 19Battery open-circuit alarm: the inverter no longer detects a battery on its terminals.
- Felicity 20Battery SOC low alarm: the battery's state of charge has fallen to the low-SOC warning threshold.
- Felicity 21BMS communication alarm: abnormal communication between battery and inverter in non-SOC mode.
Guidance reviewed 17 October 2026 by the Mishka Energy installer team. Error codes vary by brand, model family and firmware; confirm against the manufacturer manual.
Back to troubleshooting