IVGM5-8K LP2G1 hybrid inverters (warning code list, flashing fault LED)

Felicity 48 error code

Backup overload alarm: the load on the backup output is above the inverter's continuous rating and should be reduced.

Likely causes

  • Backup load above the inverter's continuous rating
  • High inrush from motors or compressors
  • Faulty appliance drawing excess current
  • Loads spread unevenly across a parallel system

Checks to run, in order

  1. 1Measure the backup load with a clamp meter and compare with the inverter rating
  2. 2Switch off loads one at a time to find the culprit
  3. 3Check for a faulty appliance or a short on one circuit
  4. 4Review start-up surge of motor loads

Fixes

  • Shed load or move non-essential circuits off the backup output
  • Stagger motor starts and fit soft starters where possible
  • Repair or replace the faulty appliance

When to escalate

If the measured load is within rating and the alarm repeats, escalate for inverter output-stage inspection.

Fix it with the right tools

Check the system around the fault before replacing parts: load, battery bank, PV string and commissioning settings. If you need a second opinion, send the code and your inverter model to our team.

Before you open the inverter

  • Isolate both the AC and DC sides, then confirm the display is dead before touching terminals.
  • Use insulated tools and one hand where possible. DC arcs do not self-extinguish like AC.
  • If you see burnt terminals, swollen cells, leaking electrolyte or a burning smell, stop and escalate instead of resetting the fault.

Questions installers ask

What does Felicity 48 mean?

Backup overload alarm: the load on the backup output is above the inverter's continuous rating and should be reduced.

How do I fix Felicity 48?

Shed load or move non-essential circuits off the backup output Stagger motor starts and fit soft starters where possible Repair or replace the faulty appliance

When should I escalate Felicity 48?

If the measured load is within rating and the alarm repeats, escalate for inverter output-stage inspection.

Can I reset Felicity 48 myself?

Only after isolating the AC and DC sides and running the checks above. If Felicity 48 returns immediately, stop resetting it and escalate; a repeating fault usually points to a real circuit, battery or hardware problem.

Which models show Felicity 48?

Felicity 48 is documented for IVGM5-8K LP2G1 hybrid inverters (warning code list, flashing fault LED). Confirm the code on your own unit's display or manual before ordering parts.