IVGM5-8K LP2G1 hybrid inverters (fault code list, solid fault LED)

Felicity 55 error code

INV under-voltage fault: the inverter's AC output voltage fell below its permitted range.

Likely causes

  • Connected load exceeds what the inverter can hold voltage into
  • Large motor or compressor starting on the backup output
  • Undersized output cabling causing voltage drop
  • Internal regulation fault

Checks to run, in order

  1. 1Measure output voltage at the inverter and at the load end
  2. 2Clamp the output current and compare with the inverter rating
  3. 3Isolate large motor loads and retest
  4. 4Check output cable size and terminations

Fixes

  • Reduce the load or stagger motor starts
  • Correct undersized or loose output cabling
  • Restart and retest with a known load

When to escalate

If the output stays low with a small resistive load and correct cabling, escalate for inverter repair.

Fix it with the right tools

Check the system around the fault before replacing parts: load, battery bank, PV string and commissioning settings. If you need a second opinion, send the code and your inverter model to our team.

Before you open the inverter

  • Isolate both the AC and DC sides, then confirm the display is dead before touching terminals.
  • Use insulated tools and one hand where possible. DC arcs do not self-extinguish like AC.
  • If you see burnt terminals, swollen cells, leaking electrolyte or a burning smell, stop and escalate instead of resetting the fault.

Questions installers ask

What does Felicity 55 mean?

INV under-voltage fault: the inverter's AC output voltage fell below its permitted range.

How do I fix Felicity 55?

Reduce the load or stagger motor starts Correct undersized or loose output cabling Restart and retest with a known load

When should I escalate Felicity 55?

If the output stays low with a small resistive load and correct cabling, escalate for inverter repair.

Can I reset Felicity 55 myself?

Only after isolating the AC and DC sides and running the checks above. If Felicity 55 returns immediately, stop resetting it and escalate; a repeating fault usually points to a real circuit, battery or hardware problem.

Which models show Felicity 55?

Felicity 55 is documented for IVGM5-8K LP2G1 hybrid inverters (fault code list, solid fault LED). Confirm the code on your own unit's display or manual before ordering parts.

More Felicity error codes

Guidance reviewed 17 October 2026 by the Mishka Energy installer team. Error codes vary by brand, model family and firmware; confirm against the manufacturer manual.

Back to troubleshooting