IVGM5-8K LP2G1 hybrid inverters (warning code list, flashing fault LED)

Felicity 62 error code

Generator reverse-sequence alarm: the phase order at the generator input is reversed.

Likely causes

  • Generator phases landed in the wrong order
  • Generator output reconnected after service with phases swapped
  • Changeover switch miswired
  • One generator phase lost

Checks to run, in order

  1. 1Measure the phase sequence at the GEN terminals
  2. 2Measure all generator phase voltages
  3. 3Check the generator output wiring and changeover switch
  4. 4Compare with the commissioning record

Fixes

  • Swap two generator phases to correct the sequence
  • Restore any missing phase or loose connection
  • Restart and confirm the generator is accepted

When to escalate

If the generator phase order is correct at the terminals and code 62 persists, escalate for GEN-input service.

Fix it with the right tools

Check the system around the fault before replacing parts: load, battery bank, PV string and commissioning settings. If you need a second opinion, send the code and your inverter model to our team.

Before you open the inverter

  • Isolate both the AC and DC sides, then confirm the display is dead before touching terminals.
  • Use insulated tools and one hand where possible. DC arcs do not self-extinguish like AC.
  • If you see burnt terminals, swollen cells, leaking electrolyte or a burning smell, stop and escalate instead of resetting the fault.

Questions installers ask

What does Felicity 62 mean?

Generator reverse-sequence alarm: the phase order at the generator input is reversed.

How do I fix Felicity 62?

Swap two generator phases to correct the sequence Restore any missing phase or loose connection Restart and confirm the generator is accepted

When should I escalate Felicity 62?

If the generator phase order is correct at the terminals and code 62 persists, escalate for GEN-input service.

Can I reset Felicity 62 myself?

Only after isolating the AC and DC sides and running the checks above. If Felicity 62 returns immediately, stop resetting it and escalate; a repeating fault usually points to a real circuit, battery or hardware problem.

Which models show Felicity 62?

Felicity 62 is documented for IVGM5-8K LP2G1 hybrid inverters (warning code list, flashing fault LED). Confirm the code on your own unit's display or manual before ordering parts.

More Felicity error codes

Guidance reviewed 17 October 2026 by the Mishka Energy installer team. Error codes vary by brand, model family and firmware; confirm against the manufacturer manual.