IVGM5-8K LP2G1 hybrid inverters (fault code list, solid fault LED)

Felicity 70 error code

AC leakage current sensor fault: the leakage-current sensor returned an implausible reading.

Likely causes

  • Failed leakage-current sensor
  • Damaged sensor harness or control-board connection
  • Moisture or corrosion on the sensor connector
  • Control-board fault

Checks to run, in order

  1. 1Confirm the inverter PE is bonded to earth
  2. 2Restart 2-3 times and note whether the code returns
  3. 3Inspect the installation for moisture or corrosion
  4. 4Arrange an installer check of the sensor harness

Fixes

  • Restart as the manual directs
  • If the code returns, remove the unit from service - leakage protection cannot be trusted
  • Book service

When to escalate

A repeated code 70 means the leakage protection is unverified - escalate to the distributor and do not leave the unit running unattended.

Fix it with the right tools

Check the system around the fault before replacing parts: load, battery bank, PV string and commissioning settings. If you need a second opinion, send the code and your inverter model to our team.

Before you open the inverter

  • Isolate both the AC and DC sides, then confirm the display is dead before touching terminals.
  • Use insulated tools and one hand where possible. DC arcs do not self-extinguish like AC.
  • If you see burnt terminals, swollen cells, leaking electrolyte or a burning smell, stop and escalate instead of resetting the fault.

Questions installers ask

What does Felicity 70 mean?

AC leakage current sensor fault: the leakage-current sensor returned an implausible reading.

How do I fix Felicity 70?

Restart as the manual directs If the code returns, remove the unit from service - leakage protection cannot be trusted Book service

When should I escalate Felicity 70?

A repeated code 70 means the leakage protection is unverified - escalate to the distributor and do not leave the unit running unattended.

Can I reset Felicity 70 myself?

Only after isolating the AC and DC sides and running the checks above. If Felicity 70 returns immediately, stop resetting it and escalate; a repeating fault usually points to a real circuit, battery or hardware problem.

Which models show Felicity 70?

Felicity 70 is documented for IVGM5-8K LP2G1 hybrid inverters (fault code list, solid fault LED). Confirm the code on your own unit's display or manual before ordering parts.

More Felicity error codes

Guidance reviewed 17 October 2026 by the Mishka Energy installer team. Error codes vary by brand, model family and firmware; confirm against the manufacturer manual.

Back to troubleshooting