IVGM5-8K LP2G1 hybrid inverters (fault code list, solid fault LED)

Felicity 72 error code

Grid relay open-circuit fault: a grid-side safety relay failed its self-check or is stuck open.

Likely causes

  • Failed grid relay
  • Relay driver or control-board fault
  • Damage after a surge or repeated switching
  • Relay stuck from a welded contact

Checks to run, in order

  1. 1Restart 2-3 times and note whether the self-check passes
  2. 2Check the grid input wiring and breaker
  3. 3Confirm the grid voltage is present at the terminals
  4. 4Do not bypass or force the relay

Fixes

  • Restart as the manual directs
  • If the self-check still fails, remove the unit from service
  • Book relay or control-board service

When to escalate

Code 72 is a safety-relay failure - escalate to the distributor; never bypass the relay to keep the site running.

Fix it with the right tools

Check the system around the fault before replacing parts: load, battery bank, PV string and commissioning settings. If you need a second opinion, send the code and your inverter model to our team.

Before you open the inverter

  • Isolate both the AC and DC sides, then confirm the display is dead before touching terminals.
  • Use insulated tools and one hand where possible. DC arcs do not self-extinguish like AC.
  • If you see burnt terminals, swollen cells, leaking electrolyte or a burning smell, stop and escalate instead of resetting the fault.

Questions installers ask

What does Felicity 72 mean?

Grid relay open-circuit fault: a grid-side safety relay failed its self-check or is stuck open.

How do I fix Felicity 72?

Restart as the manual directs If the self-check still fails, remove the unit from service Book relay or control-board service

When should I escalate Felicity 72?

Code 72 is a safety-relay failure - escalate to the distributor; never bypass the relay to keep the site running.

Can I reset Felicity 72 myself?

Only after isolating the AC and DC sides and running the checks above. If Felicity 72 returns immediately, stop resetting it and escalate; a repeating fault usually points to a real circuit, battery or hardware problem.

Which models show Felicity 72?

Felicity 72 is documented for IVGM5-8K LP2G1 hybrid inverters (fault code list, solid fault LED). Confirm the code on your own unit's display or manual before ordering parts.