IVGM5-8K LP2G1 hybrid inverters (fault code list, solid fault LED)

Felicity 77 error code

PV insulation impedance fault: the PV array's resistance to earth is below the safe threshold.

Likely causes

  • Damaged PV cable insulation
  • Water or moisture in a connector or junction box
  • Inverter PE not connected to ground
  • Dirty or degraded PV connectors
  • Long, wet cable runs with damaged conduit

Checks to run, in order

  1. 1Check that the PV panels and inverter are firmly and correctly connected
  2. 2Check that the inverter's PE cable is connected to ground
  3. 3Measure insulation resistance from each string to earth
  4. 4Inspect connectors and cable runs for damage or water

Fixes

  • Repair or replace damaged DC cabling and connectors
  • Dry the array and reseal wet joints
  • Restore the PE connection, then restart 2-3 times

When to escalate

If insulation resistance stays low after damaged cabling is repaired and the array is dry, escalate for a full string insulation test and inverter check.

Fix it with the right tools

Check the system around the fault before replacing parts: load, battery bank, PV string and commissioning settings. If you need a second opinion, send the code and your inverter model to our team.

Before you open the inverter

  • Isolate both the AC and DC sides, then confirm the display is dead before touching terminals.
  • Use insulated tools and one hand where possible. DC arcs do not self-extinguish like AC.
  • If you see burnt terminals, swollen cells, leaking electrolyte or a burning smell, stop and escalate instead of resetting the fault.

Questions installers ask

What does Felicity 77 mean?

PV insulation impedance fault: the PV array's resistance to earth is below the safe threshold.

How do I fix Felicity 77?

Repair or replace damaged DC cabling and connectors Dry the array and reseal wet joints Restore the PE connection, then restart 2-3 times

When should I escalate Felicity 77?

If insulation resistance stays low after damaged cabling is repaired and the array is dry, escalate for a full string insulation test and inverter check.

Can I reset Felicity 77 myself?

Only after isolating the AC and DC sides and running the checks above. If Felicity 77 returns immediately, stop resetting it and escalate; a repeating fault usually points to a real circuit, battery or hardware problem.

Which models show Felicity 77?

Felicity 77 is documented for IVGM5-8K LP2G1 hybrid inverters (fault code list, solid fault LED). Confirm the code on your own unit's display or manual before ordering parts.