IVGM5-8K LP2G1 hybrid inverters (fault code list, solid fault LED)

Felicity 94 error code

CAN ID conflict: two inverters in the parallel system share a CAN ID, or two masters exist in one phase.

Likely causes

  • Duplicate CAN address on two units
  • Two inverters configured as master in the same phase
  • Address changed without updating the others
  • Commissioning error

Checks to run, in order

  1. 1Read the CAN ID on every inverter in the group
  2. 2Check which unit is configured as master in each phase
  3. 3Compare the addresses with the commissioning sheet
  4. 4Look for two units set to the same address

Fixes

  • Give every unit a unique CAN ID
  • Leave only one master per phase
  • Restart the group and confirm the conflict clears

When to escalate

If the addresses are unique and only one master exists per phase but code 94 persists, escalate for parallel-control service.

Fix it with the right tools

Check the system around the fault before replacing parts: load, battery bank, PV string and commissioning settings. If you need a second opinion, send the code and your inverter model to our team.

Before you open the inverter

  • Isolate both the AC and DC sides, then confirm the display is dead before touching terminals.
  • Use insulated tools and one hand where possible. DC arcs do not self-extinguish like AC.
  • If you see burnt terminals, swollen cells, leaking electrolyte or a burning smell, stop and escalate instead of resetting the fault.

Questions installers ask

What does Felicity 94 mean?

CAN ID conflict: two inverters in the parallel system share a CAN ID, or two masters exist in one phase.

How do I fix Felicity 94?

Give every unit a unique CAN ID Leave only one master per phase Restart the group and confirm the conflict clears

When should I escalate Felicity 94?

If the addresses are unique and only one master exists per phase but code 94 persists, escalate for parallel-control service.

Can I reset Felicity 94 myself?

Only after isolating the AC and DC sides and running the checks above. If Felicity 94 returns immediately, stop resetting it and escalate; a repeating fault usually points to a real circuit, battery or hardware problem.

Which models show Felicity 94?

Felicity 94 is documented for IVGM5-8K LP2G1 hybrid inverters (fault code list, solid fault LED). Confirm the code on your own unit's display or manual before ordering parts.