IVGM5-8K LP2G1 hybrid inverters (fault code list, solid fault LED)

Felicity 96 error code

Phase sequence abnormal: the phase order at the grid input is incorrect.

Likely causes

  • Grid phases landed in the wrong order
  • Generator phases in the wrong order
  • Wiring changed at the main distribution board
  • Phase loss combined with a sequencing error

Checks to run, in order

  1. 1Measure the phase sequence at the inverter grid terminals
  2. 2Measure all three phase-to-neutral and phase-to-phase voltages
  3. 3Compare the wiring with the installation drawing and the meter's phase order
  4. 4Check the generator phase order if a generator is used

Fixes

  • Swap two phases to correct the sequence
  • Restore any missing phase or loose connection
  • Restart and confirm the inverter synchronises

When to escalate

If the phase order is correct at the terminals and code 96 persists, escalate for inverter input-board service.

Fix it with the right tools

Check the system around the fault before replacing parts: load, battery bank, PV string and commissioning settings. If you need a second opinion, send the code and your inverter model to our team.

Before you open the inverter

  • Isolate both the AC and DC sides, then confirm the display is dead before touching terminals.
  • Use insulated tools and one hand where possible. DC arcs do not self-extinguish like AC.
  • If you see burnt terminals, swollen cells, leaking electrolyte or a burning smell, stop and escalate instead of resetting the fault.

Questions installers ask

What does Felicity 96 mean?

Phase sequence abnormal: the phase order at the grid input is incorrect.

How do I fix Felicity 96?

Swap two phases to correct the sequence Restore any missing phase or loose connection Restart and confirm the inverter synchronises

When should I escalate Felicity 96?

If the phase order is correct at the terminals and code 96 persists, escalate for inverter input-board service.

Can I reset Felicity 96 myself?

Only after isolating the AC and DC sides and running the checks above. If Felicity 96 returns immediately, stop resetting it and escalate; a repeating fault usually points to a real circuit, battery or hardware problem.

Which models show Felicity 96?

Felicity 96 is documented for IVGM5-8K LP2G1 hybrid inverters (fault code list, solid fault LED). Confirm the code on your own unit's display or manual before ordering parts.

More Felicity error codes

Guidance reviewed 17 October 2026 by the Mishka Energy installer team. Error codes vary by brand, model family and firmware; confirm against the manufacturer manual.