IPV series (IPV-4K24U, IPV-6K48U, IPV-4K24U Pro, IPV-6K48U Pro, IPV-12K48U) — inverter fault code
Itel Energy 60 error code
CAN communication between the parallel units has been lost.
Likely causes
- CAN cable loose or plugged into the wrong port
- Damaged CAN cable or connector
- One unit switched off or faulted
- Missing or incorrect CAN termination
Checks to run, in order
- 1Check the CAN cable at both ends of every unit
- 2Confirm all units are powered and not showing another fault
- 3Swap the CAN cable with a known-good one to test
- 4Check the parallel addressing on each unit
Fixes
- Reseat or replace the CAN cable
- Correct the parallel addressing
- Restart the system and confirm the fault clears
When to escalate
If CAN wiring and termination are correct across all units, escalate to the distributor with unit count and firmware versions.
Fix it with the right tools
Check the system around the fault before replacing parts: load, battery bank, PV string and commissioning settings. If you need a second opinion, send the code and your inverter model to our team.
Before you open the inverter
- Isolate both the AC and DC sides, then confirm the display is dead before touching terminals.
- Use insulated tools and one hand where possible. DC arcs do not self-extinguish like AC.
- If you see burnt terminals, swollen cells, leaking electrolyte or a burning smell, stop and escalate instead of resetting the fault.
Questions installers ask
What does Itel Energy 60 mean?
CAN communication between the parallel units has been lost.
How do I fix Itel Energy 60?
Reseat or replace the CAN cable Correct the parallel addressing Restart the system and confirm the fault clears
When should I escalate Itel Energy 60?
If CAN wiring and termination are correct across all units, escalate to the distributor with unit count and firmware versions.
Can I reset Itel Energy 60 myself?
Only after isolating the AC and DC sides and running the checks above. If Itel Energy 60 returns immediately, stop resetting it and escalate; a repeating fault usually points to a real circuit, battery or hardware problem.
Which models show Itel Energy 60?
Itel Energy 60 is documented for IPV series (IPV-4K24U, IPV-6K48U, IPV-4K24U Pro, IPV-6K48U Pro, IPV-12K48U) — inverter fault code. Confirm the code on your own unit's display or manual before ordering parts.
More Itel Energy error codes
- Itel Energy 01Display code 01 covers two events: as a warning it signals output overload (flashing fault LED, two beeps per second); as a fault it signals DC bus over-voltage (solid fault LED, output switched off).
- Itel Energy 02Display code 02 covers two events: as a warning it signals the upper cooling fan is locked (three beeps); as a fault it signals DC bus under-voltage (solid fault LED, output switched off).
- Itel Energy 03Display code 03 covers two events: as a warning it signals the lower cooling fan is locked (three beeps); as a fault it signals that the DC bus soft-start sequence failed (solid fault LED).
- Itel Energy 04Grid voltage is above the upper limit of the inverter's grid window; warning only, with no buzzer alarm.
- Itel Energy 05In a parallel system the AC outputs of the units are not connected together, or a unit is running on a different phase.
- Itel Energy 06Remote shutdown is enabled, typically from the monitoring app over Wi-Fi, so the inverter is being held off remotely.
Guidance reviewed 17 October 2026 by the Mishka Energy installer team. Error codes vary by brand, model family and firmware; confirm against the manufacturer manual.
Back to troubleshooting