Anern AN-SCI-EVO OEM series (SMS 2 kVA/12 V, 4.2 kW/24 V, 10.2 kVA/48 V hybrid units)

SMS Sunmate Solar 03 error code

Battery over-voltage: the battery bank is charged above the inverter's high-voltage limit. The same number is also used as a warning (beep once per second) when the battery is overcharged.

Likely causes

  • Battery type or charge voltage setting not matched to the installed bank
  • Too much PV or charger current for the size of the bank
  • Battery count or bank voltage different from the specification
  • External charger or BMS pushing the bank too high

Checks to run, in order

  1. 1Measure the battery voltage at the terminals with a multimeter and compare it with the display
  2. 2Check that the battery count and nominal voltage match the model specification
  3. 3Review the battery type and charge voltage settings
  4. 4Check whether an external charger or BMS is raising the voltage

Fixes

  • Correct the battery type and charge voltage settings
  • Disconnect any external charger until the voltage falls back into range
  • Stop charging and have an overcharged bank inspected before reuse

When to escalate

The manual directs an overcharged battery to the repair centre: stop using the bank and have the distributor check the charger and BMS.

Fix it with the right tools

Check the system around the fault before replacing parts: load, battery bank, PV string and commissioning settings. If you need a second opinion, send the code and your inverter model to our team.

Before you open the inverter

  • Isolate both the AC and DC sides, then confirm the display is dead before touching terminals.
  • Use insulated tools and one hand where possible. DC arcs do not self-extinguish like AC.
  • If you see burnt terminals, swollen cells, leaking electrolyte or a burning smell, stop and escalate instead of resetting the fault.

Questions installers ask

What does SMS Sunmate Solar 03 mean?

Battery over-voltage: the battery bank is charged above the inverter's high-voltage limit. The same number is also used as a warning (beep once per second) when the battery is overcharged.

How do I fix SMS Sunmate Solar 03?

Correct the battery type and charge voltage settings Disconnect any external charger until the voltage falls back into range Stop charging and have an overcharged bank inspected before reuse

When should I escalate SMS Sunmate Solar 03?

The manual directs an overcharged battery to the repair centre: stop using the bank and have the distributor check the charger and BMS.

Can I reset SMS Sunmate Solar 03 myself?

Only after isolating the AC and DC sides and running the checks above. If SMS Sunmate Solar 03 returns immediately, stop resetting it and escalate; a repeating fault usually points to a real circuit, battery or hardware problem.

Which models show SMS Sunmate Solar 03?

SMS Sunmate Solar 03 is documented for Anern AN-SCI-EVO OEM series (SMS 2 kVA/12 V, 4.2 kW/24 V, 10.2 kVA/48 V hybrid units). Confirm the code on your own unit's display or manual before ordering parts.

More SMS Sunmate Solar error codes

Guidance reviewed 17 October 2026 by the Mishka Energy installer team. Error codes vary by brand, model family and firmware; confirm against the manufacturer manual.