Anern AN-SCI-EVO OEM series (SMS 2 kVA/12 V, 4.2 kW/24 V, 10.2 kVA/48 V hybrid units)
SMS Sunmate Solar 58 error code
Abnormal output voltage: the inverter output is below 190 V AC (the manual groups 06 and 58 as output voltage outside the 190–260 V AC band).
Likely causes
- Overload pulling the output voltage down
- Output stage fault
- Voltage drop on long or undersized output cabling
- Load with a very high inrush at start-up
Checks to run, in order
- 1Measure the output at the inverter terminals with a true-RMS meter under load
- 2Measure again at the load end to see the cable drop
- 3Disconnect loads one at a time and watch the voltage recover
- 4Check the output cable size and run length
Fixes
- Reduce the load and retest
- Replace undersized or long output cabling
- Restart after the load is corrected
When to escalate
If the output stays below 190 V with no load and healthy cabling, the output stage is faulty — return the unit for service.
Fix it with the right tools
Check the system around the fault before replacing parts: load, battery bank, PV string and commissioning settings. If you need a second opinion, send the code and your inverter model to our team.
Before you open the inverter
- Isolate both the AC and DC sides, then confirm the display is dead before touching terminals.
- Use insulated tools and one hand where possible. DC arcs do not self-extinguish like AC.
- If you see burnt terminals, swollen cells, leaking electrolyte or a burning smell, stop and escalate instead of resetting the fault.
Questions installers ask
What does SMS Sunmate Solar 58 mean?
Abnormal output voltage: the inverter output is below 190 V AC (the manual groups 06 and 58 as output voltage outside the 190–260 V AC band).
How do I fix SMS Sunmate Solar 58?
Reduce the load and retest Replace undersized or long output cabling Restart after the load is corrected
When should I escalate SMS Sunmate Solar 58?
If the output stays below 190 V with no load and healthy cabling, the output stage is faulty — return the unit for service.
Can I reset SMS Sunmate Solar 58 myself?
Only after isolating the AC and DC sides and running the checks above. If SMS Sunmate Solar 58 returns immediately, stop resetting it and escalate; a repeating fault usually points to a real circuit, battery or hardware problem.
Which models show SMS Sunmate Solar 58?
SMS Sunmate Solar 58 is documented for Anern AN-SCI-EVO OEM series (SMS 2 kVA/12 V, 4.2 kW/24 V, 10.2 kVA/48 V hybrid units). Confirm the code on your own unit's display or manual before ordering parts.
More SMS Sunmate Solar error codes
- SMS Sunmate Solar 01Fan failure: the cooling fan is blocked or not turning. The same code appears as a warning when the fan is blocked while the inverter is running.
- SMS Sunmate Solar 02Over-temperature: internal component temperature above 100 °C, or converter temperature above 120 °C.
- SMS Sunmate Solar 03Battery over-voltage: the battery bank is charged above the inverter's high-voltage limit. The same number is also used as a warning (beep once per second) when the battery is overcharged.
- SMS Sunmate Solar 04Battery under-voltage: the bank has discharged below the inverter's low-voltage cutoff. The same number is also used as a low-battery warning (beep once per second).
- SMS Sunmate Solar 05Output short circuit: a short is detected on the AC output.
- SMS Sunmate Solar 06Abnormal output voltage: the inverter output is above 260 V AC (the manual groups 06 and 58 as output voltage outside the 190–260 V AC band).
Guidance reviewed 17 October 2026 by the Mishka Energy installer team. Error codes vary by brand, model family and firmware; confirm against the manufacturer manual.
Back to troubleshooting