Anern AN-SCI-EVO OEM series (SMS 2 kVA/12 V, 4.2 kW/24 V, 10.2 kVA/48 V hybrid units)

SMS Sunmate Solar 58 error code

Abnormal output voltage: the inverter output is below 190 V AC (the manual groups 06 and 58 as output voltage outside the 190–260 V AC band).

Likely causes

  • Overload pulling the output voltage down
  • Output stage fault
  • Voltage drop on long or undersized output cabling
  • Load with a very high inrush at start-up

Checks to run, in order

  1. 1Measure the output at the inverter terminals with a true-RMS meter under load
  2. 2Measure again at the load end to see the cable drop
  3. 3Disconnect loads one at a time and watch the voltage recover
  4. 4Check the output cable size and run length

Fixes

  • Reduce the load and retest
  • Replace undersized or long output cabling
  • Restart after the load is corrected

When to escalate

If the output stays below 190 V with no load and healthy cabling, the output stage is faulty — return the unit for service.

Fix it with the right tools

Check the system around the fault before replacing parts: load, battery bank, PV string and commissioning settings. If you need a second opinion, send the code and your inverter model to our team.

Before you open the inverter

  • Isolate both the AC and DC sides, then confirm the display is dead before touching terminals.
  • Use insulated tools and one hand where possible. DC arcs do not self-extinguish like AC.
  • If you see burnt terminals, swollen cells, leaking electrolyte or a burning smell, stop and escalate instead of resetting the fault.

Questions installers ask

What does SMS Sunmate Solar 58 mean?

Abnormal output voltage: the inverter output is below 190 V AC (the manual groups 06 and 58 as output voltage outside the 190–260 V AC band).

How do I fix SMS Sunmate Solar 58?

Reduce the load and retest Replace undersized or long output cabling Restart after the load is corrected

When should I escalate SMS Sunmate Solar 58?

If the output stays below 190 V with no load and healthy cabling, the output stage is faulty — return the unit for service.

Can I reset SMS Sunmate Solar 58 myself?

Only after isolating the AC and DC sides and running the checks above. If SMS Sunmate Solar 58 returns immediately, stop resetting it and escalate; a repeating fault usually points to a real circuit, battery or hardware problem.

Which models show SMS Sunmate Solar 58?

SMS Sunmate Solar 58 is documented for Anern AN-SCI-EVO OEM series (SMS 2 kVA/12 V, 4.2 kW/24 V, 10.2 kVA/48 V hybrid units). Confirm the code on your own unit's display or manual before ordering parts.

More SMS Sunmate Solar error codes

Guidance reviewed 17 October 2026 by the Mishka Energy installer team. Error codes vary by brand, model family and firmware; confirm against the manufacturer manual.

Back to troubleshooting