HESP series hybrid inverters (single-phase 4-12 kW and three-phase 8-12 kW)

SRNE 15 error code

Inverter overcurrent detected by hardware protection (AcOverCurrHw); the output is switched off.

Likely causes

  • Short circuit on the AC output
  • Earth fault on the load wiring
  • Water ingress into an outdoor circuit
  • Internal output-stage fault

Checks to run, in order

  1. 1Disconnect all load circuits and check output insulation resistance
  2. 2Inspect the AC output terminals and cable for burning
  3. 3Check for water ingress in outdoor junction boxes
  4. 4Test the output with only a small known load

Fixes

  • Clear the short or earth fault before restarting
  • Replace damaged output cabling
  • Restart once the output circuits test clean

When to escalate

A hardware output overcurrent fault with no load-side fault means the output stage has failed; refer it to the distributor.

Fix it with the right tools

Check the system around the fault before replacing parts: load, battery bank, PV string and commissioning settings. If you need a second opinion, send the code and your inverter model to our team.

Before you open the inverter

  • Isolate both the AC and DC sides, then confirm the display is dead before touching terminals.
  • Use insulated tools and one hand where possible. DC arcs do not self-extinguish like AC.
  • If you see burnt terminals, swollen cells, leaking electrolyte or a burning smell, stop and escalate instead of resetting the fault.

Questions installers ask

What does SRNE 15 mean?

Inverter overcurrent detected by hardware protection (AcOverCurrHw); the output is switched off.

How do I fix SRNE 15?

Clear the short or earth fault before restarting Replace damaged output cabling Restart once the output circuits test clean

When should I escalate SRNE 15?

A hardware output overcurrent fault with no load-side fault means the output stage has failed; refer it to the distributor.

Can I reset SRNE 15 myself?

Only after isolating the AC and DC sides and running the checks above. If SRNE 15 returns immediately, stop resetting it and escalate; a repeating fault usually points to a real circuit, battery or hardware problem.

Which models show SRNE 15?

SRNE 15 is documented for HESP series hybrid inverters (single-phase 4-12 kW and three-phase 8-12 kW). Confirm the code on your own unit's display or manual before ordering parts.