HESP series hybrid inverters (single-phase 4-12 kW and three-phase 8-12 kW)

SRNE 26 error code

Relay short / AC output backfeeding to the bypass AC input (RlyShort): the AC input relay is stuck or output voltage is reaching the AC input.

Likely causes

  • Welded AC input relay
  • Output wiring tied to the AC input
  • Backfeed from a generator connected to the output
  • Relay driver circuit failure

Checks to run, in order

  1. 1With the inverter off and the AC input isolated, check for voltage on the AC input terminals
  2. 2Verify the output and input circuits are not interconnected
  3. 3Check for a generator or other source connected on the output side
  4. 4Confirm the wiring against the manual's terminal diagram

Fixes

  • Correct any input/output interconnection
  • Replace the relay board through the distributor
  • Restart only after the wiring is verified

When to escalate

A welded relay is not field-repairable, and backfeed is a shock hazard: isolate the unit and call the distributor immediately.

Fix it with the right tools

Check the system around the fault before replacing parts: load, battery bank, PV string and commissioning settings. If you need a second opinion, send the code and your inverter model to our team.

Before you open the inverter

  • Isolate both the AC and DC sides, then confirm the display is dead before touching terminals.
  • Use insulated tools and one hand where possible. DC arcs do not self-extinguish like AC.
  • If you see burnt terminals, swollen cells, leaking electrolyte or a burning smell, stop and escalate instead of resetting the fault.

Questions installers ask

What does SRNE 26 mean?

Relay short / AC output backfeeding to the bypass AC input (RlyShort): the AC input relay is stuck or output voltage is reaching the AC input.

How do I fix SRNE 26?

Correct any input/output interconnection Replace the relay board through the distributor Restart only after the wiring is verified

When should I escalate SRNE 26?

A welded relay is not field-repairable, and backfeed is a shock hazard: isolate the unit and call the distributor immediately.

Can I reset SRNE 26 myself?

Only after isolating the AC and DC sides and running the checks above. If SRNE 26 returns immediately, stop resetting it and escalate; a repeating fault usually points to a real circuit, battery or hardware problem.

Which models show SRNE 26?

SRNE 26 is documented for HESP series hybrid inverters (single-phase 4-12 kW and three-phase 8-12 kW). Confirm the code on your own unit's display or manual before ordering parts.