SUN-5-12K-SG01HP3-EU-DM2 three-phase hybrid (F-series table)

Deye F27 error code

DC insulation fault reported by the second detection path.

Likely causes

  • Damaged PV cable or connector insulation
  • Moisture in the array wiring
  • Inverter PE not connected
  • Insulation-detection circuit fault

Checks to run, in order

  1. 1Megger the PV strings to earth
  2. 2Inspect DC cables and connectors
  3. 3Check the inverter PE bond
  4. 4Restart and read the fault log

Fixes

  • Repair the damaged insulation
  • Bond the PE conductor
  • Restart three times and restore factory settings

When to escalate

If the array insulation is healthy and F27 persists, the distributor should check the insulation-detection circuit.

Fix it with the right tools

Check the system around the fault before replacing parts: load, battery bank, PV string and commissioning settings. If you need a second opinion, send the code and your inverter model to our team.

Before you open the inverter

  • Isolate both the AC and DC sides, then confirm the display is dead before touching terminals.
  • Use insulated tools and one hand where possible. DC arcs do not self-extinguish like AC.
  • If you see burnt terminals, swollen cells, leaking electrolyte or a burning smell, stop and escalate instead of resetting the fault.

Questions installers ask

What does Deye F27 mean?

DC insulation fault reported by the second detection path.

How do I fix Deye F27?

Repair the damaged insulation Bond the PE conductor Restart three times and restore factory settings

When should I escalate Deye F27?

If the array insulation is healthy and F27 persists, the distributor should check the insulation-detection circuit.

Can I reset Deye F27 myself?

Only after isolating the AC and DC sides and running the checks above. If Deye F27 returns immediately, stop resetting it and escalate; a repeating fault usually points to a real circuit, battery or hardware problem.

Which models show Deye F27?

Deye F27 is documented for SUN-5-12K-SG01HP3-EU-DM2 three-phase hybrid (F-series table). Confirm the code on your own unit's display or manual before ordering parts.