SUN-5-12K-SG01HP3-EU-DM2 three-phase hybrid (F-series table)

Deye F57 error code

Battery 2 terminal voltage too low.

Likely causes

  • Deep discharge of the second battery bank
  • Battery 2 breaker or BMS contactor open
  • Wrong low-voltage cutoff setting
  • Voltage-sensing or wiring fault

Checks to run, in order

  1. 1Measure the battery 2 terminal voltage
  2. 2Check the battery 2 breaker and BMS
  3. 3Check the low-voltage cutoff setting
  4. 4Check the battery 2 wiring

Fixes

  • Charge the battery 2 bank
  • Correct the low-voltage cutoff setting
  • Restart twice and restore factory settings

When to escalate

If the battery 2 voltage is correct and F57 persists, the distributor should check the battery voltage sensing.

Fix it with the right tools

Check the system around the fault before replacing parts: load, battery bank, PV string and commissioning settings. If you need a second opinion, send the code and your inverter model to our team.

Before you open the inverter

  • Isolate both the AC and DC sides, then confirm the display is dead before touching terminals.
  • Use insulated tools and one hand where possible. DC arcs do not self-extinguish like AC.
  • If you see burnt terminals, swollen cells, leaking electrolyte or a burning smell, stop and escalate instead of resetting the fault.

Questions installers ask

What does Deye F57 mean?

Battery 2 terminal voltage too low.

How do I fix Deye F57?

Charge the battery 2 bank Correct the low-voltage cutoff setting Restart twice and restore factory settings

When should I escalate Deye F57?

If the battery 2 voltage is correct and F57 persists, the distributor should check the battery voltage sensing.

Can I reset Deye F57 myself?

Only after isolating the AC and DC sides and running the checks above. If Deye F57 returns immediately, stop resetting it and escalate; a repeating fault usually points to a real circuit, battery or hardware problem.

Which models show Deye F57?

Deye F57 is documented for SUN-5-12K-SG01HP3-EU-DM2 three-phase hybrid (F-series table). Confirm the code on your own unit's display or manual before ordering parts.