SG04LP3/SG05LP1 hybrid families and SG01HP3-EU-DM2

Deye F58 error code

Battery BMS communication lost while 'BMS_Err-Stop' is enabled.

Likely causes

  • CAN or RS485 cable disconnected
  • Wrong BMS protocol or baud rate
  • BMS powered down
  • Address or protocol mismatch

Checks to run, in order

  1. 1Check the BMS communication cable
  2. 2Check the BMS protocol setting
  3. 3Check BMS power and status
  4. 4Check the termination resistor

Fixes

  • Reseat or replace the communication cable
  • Set the correct BMS protocol
  • Restart the inverter and BMS
  • Disable 'BMS_Err-Stop' only if the battery is set up for voltage-mode operation

When to escalate

If communication cannot be restored, involve the distributor and the battery supplier together.

Fix it with the right tools

Check the system around the fault before replacing parts: load, battery bank, PV string and commissioning settings. If you need a second opinion, send the code and your inverter model to our team.

Before you open the inverter

  • Isolate both the AC and DC sides, then confirm the display is dead before touching terminals.
  • Use insulated tools and one hand where possible. DC arcs do not self-extinguish like AC.
  • If you see burnt terminals, swollen cells, leaking electrolyte or a burning smell, stop and escalate instead of resetting the fault.

Questions installers ask

What does Deye F58 mean?

Battery BMS communication lost while 'BMS_Err-Stop' is enabled.

How do I fix Deye F58?

Reseat or replace the communication cable Set the correct BMS protocol Restart the inverter and BMS Disable 'BMS_Err-Stop' only if the battery is set up for voltage-mode operation

When should I escalate Deye F58?

If communication cannot be restored, involve the distributor and the battery supplier together.

Can I reset Deye F58 myself?

Only after isolating the AC and DC sides and running the checks above. If Deye F58 returns immediately, stop resetting it and escalate; a repeating fault usually points to a real circuit, battery or hardware problem.

Which models show Deye F58?

Deye F58 is documented for SG04LP3/SG05LP1 hybrid families and SG01HP3-EU-DM2. Confirm the code on your own unit's display or manual before ordering parts.