SPH 3000–6000TL BL-UP / SPH 4000–10000TL3 BH-UP hybrid (Error 2xx–6xx codes)

Growatt Error 505 error code

Battery polarity is reversed at the inverter battery input.

Likely causes

  • Battery positive and negative cables swapped
  • Reversed extension cable or wrongly labelled battery terminal
  • Battery bank reconnected after maintenance with polarity reversed

Checks to run, in order

  1. 1Isolate the battery and measure polarity at the inverter battery terminals
  2. 2Inspect cable ends and lug labelling against the battery terminals
  3. 3Check whether a battery fuse or breaker has opened during the event

Fixes

  • Correct the battery polarity and re-terminate the cables
  • Replace any fuse that opened during the reverse connection
  • Restart the inverter and verify battery voltage and charging

When to escalate

If polarity is correct and Error 505 persists, the battery input protection may be damaged — return the inverter to Growatt service.

Fix it with the right tools

Check the system around the fault before replacing parts: load, battery bank, PV string and commissioning settings. If you need a second opinion, send the code and your inverter model to our team.

Before you open the inverter

  • Isolate both the AC and DC sides, then confirm the display is dead before touching terminals.
  • Use insulated tools and one hand where possible. DC arcs do not self-extinguish like AC.
  • If you see burnt terminals, swollen cells, leaking electrolyte or a burning smell, stop and escalate instead of resetting the fault.

Questions installers ask

What does Growatt Error 505 mean?

Battery polarity is reversed at the inverter battery input.

How do I fix Growatt Error 505?

Correct the battery polarity and re-terminate the cables Replace any fuse that opened during the reverse connection Restart the inverter and verify battery voltage and charging

When should I escalate Growatt Error 505?

If polarity is correct and Error 505 persists, the battery input protection may be damaged — return the inverter to Growatt service.

Can I reset Growatt Error 505 myself?

Only after isolating the AC and DC sides and running the checks above. If Growatt Error 505 returns immediately, stop resetting it and escalate; a repeating fault usually points to a real circuit, battery or hardware problem.

Which models show Growatt Error 505?

Growatt Error 505 is documented for SPH 3000–6000TL BL-UP / SPH 4000–10000TL3 BH-UP hybrid (Error 2xx–6xx codes). Confirm the code on your own unit's display or manual before ordering parts.

More Growatt error codes

Guidance reviewed 17 October 2026 by the Mishka Energy installer team. Error codes vary by brand, model family and firmware; confirm against the manufacturer manual.