Error code library · 30 codes
Beve error codes
Every Beve error and fault code we have documented for MEGA 6/8/10/12 kW single-phase hybrid inverter — inverter fault and MEGA 6/8/10/12 kW single-phase hybrid inverter — battery BMS communication fault. Each code has its own guide: what it means, the likely causes, checks to run in order, fixes and when to escalate. Compiled from Beve manuals; always confirm the code on your own unit and firmware.
MEGA 6/8/10/12 kW single-phase hybrid inverter — inverter fault29 codes
- Beve 01Cooling fan is locked and not turning while the inverter is switched on.
- Beve 02Inverter temperature has exceeded its protection point.
- Beve 03Battery voltage is above the inverter's high battery cut-off.
- Beve 05Output short circuit detected on the inverter AC output.
- Beve 06Inverter output voltage is above the acceptable window; the manual's troubleshooting table puts this above 260 Vac.
- Beve 07Overload: the inverter has been running above its rating (102% in the manual's note) until the overload time expired.
- Beve 08Internal DC bus voltage is above its limit.
- Beve 12The inverter's soft-start sequence failed.
- Beve 15Internal communication (SCI) between the inverter's control boards has failed.
- Beve 17LLC resonant converter short-circuit fault.
- Beve 19PV input current is above the channel limit (18 A per PV input on this series).
- Beve 21Leakage current (GFCI) fault detected on the AC output.
- Beve 23PV isolation resistance to earth is too low.
- Beve 25The inverter's AC relay self-check failed.
- Beve 51Over-current or surge on the inverter output.
- Beve 52Internal DC bus voltage is below its limit.
- Beve 53Inverter soft start failed: the power stage could not bring the output up.
- Beve 55Excessive DC voltage component in the AC output; the manual's troubleshooting table also describes this as output voltage unbalanced.
- Beve 57Current sensor (Hall sensor) failure.
- Beve 58Inverter output voltage is below the acceptable window; the manual's troubleshooting table puts this below 190 Vac.
- Beve 59PV input voltage exceeds the inverter's maximum of 520 Vdc.
- Beve 60Parallel failure: the code name refers to negative (reverse) power on a unit in the parallel system; the manual's description is simply 'Parallel failure'.
- Beve 71Parallel version inconsistent: the units in a parallel system report different versions.
- Beve 75Parallel settings inconsistent between the units in the system.
- Beve 80Parallel communication failure between units.
- Beve 81Host signal lost: the master unit's signal is not reaching the slave units.
- Beve 82Synchronisation signal loss between parallel units.
- Beve 86Parallel mode is incorrect: a unit is set to a mode that does not match the rest of the system.
- Beve 99Other fault: an internal fault that the firmware does not map to a specific code.
MEGA 6/8/10/12 kW single-phase hybrid inverter — battery BMS communication fault1 codes
Before you reset a Beve fault
- 1Write down the exact code and any letter before it, and check which Beve model is showing it. The same number can mean different faults on an inverter and on a battery.
- 2Isolate the AC and DC sides before touching terminals, then run the checks on the code's page in order.
- 3If the code comes straight back after a reset, stop resetting it. A repeating fault points to a real wiring, battery or hardware problem.