Error code library · 69 codes
Deye error codes
Every Deye error and fault code we have documented for SG04LP3/SG05LP1 hybrid families and SG01HP3-EU-DM2, SUN-5-12K-SG01HP3-EU-DM2 three-phase hybrid (F-series table), Hybrid inverters (F-series fault codes) and SUN-5-12K-SG01HP3-EU-DM2 three-phase hybrid (warning codes). Each code has its own guide: what it means, the likely causes, checks to run in order, fixes and when to escalate. Compiled from Deye manuals; always confirm the code on your own unit and firmware.
SG04LP3/SG05LP1 hybrid families and SG01HP3-EU-DM225 codes
- Deye F01PV input polarity is reversed at one or both DC inputs.
- Deye F07DC-DC stage 1 could not raise the bus voltage from PV or battery.
- Deye F08DC-DC stage 2 could not raise the bus voltage from PV or battery.
- Deye F15AC output overcurrent detected in software (backup or common load).
- Deye F16Leakage current (GFCI) fault.
- Deye F18AC overcurrent detected by hardware.
- Deye F20DC overcurrent detected by hardware; common when starting a heavy off-grid load.
- Deye F21DC bus overcurrent.
- Deye F22Remote emergency stop or remote shutdown command is active.
- Deye F23Transient AC leakage current above the limit.
- Deye F24PV isolation resistance too low.
- Deye F26DC bus voltage is unbalanced.
- Deye F29Parallel communication fault between paralleled inverters.
- Deye F34AC overload on the backup output.
- Deye F35No AC grid supply detected.
- Deye F41Parallel system stop: at least one inverter in the parallel system is off or stopped.
- Deye F42On SG04LP3/SG05LP1, the grid/AC line voltage is below the configured low-voltage limit; on SG01HP3-DM2 firmware F42 instead reports a parallel software-version mismatch.
- Deye F46On SG04LP3/SG05LP1, a backup-battery fault: parallel batteries have mismatched voltage, SOC or parameters; on SG01HP3-DM2 firmware F46 instead reports AC grid undervoltage.
- Deye F47Grid frequency above the configured range.
- Deye F48Grid frequency below the configured range.
- Deye F55On SG04LP3/SG05LP1, DC bus voltage too high; on SG01HP3-DM2 firmware F55 reports battery 1 terminal voltage too high.
- Deye F58Battery BMS communication lost while 'BMS_Err-Stop' is enabled.
- Deye F62DRMs_Stop: demand-response (DRM) stop is active.
- Deye F63ARC fault (DC arc) detected; arc detection is provided for the US market.
- Deye F64Heatsink temperature too high.
SUN-5-12K-SG01HP3-EU-DM2 three-phase hybrid (F-series table)31 codes
- Deye F02PV insulation resistance to earth is below the safety limit.
- Deye F03Ground fault detected on the PV array (GFDI).
- Deye F04GFDI ground-failure alarm: the PV array or inverter is not properly earthed.
- Deye F05Control-board EEPROM read failure.
- Deye F06Control-board EEPROM write failure.
- Deye F09IGBT power-stage failure detected.
- Deye F10Auxiliary power-supply board failure.
- Deye F11AC main contactor failed to close or report correctly.
- Deye F12AC slave contactor failed to close or report correctly.
- Deye F14DC overcurrent detected by the control firmware.
- Deye F17PV input overcurrent.
- Deye F19Internal consistency (integration) fault in the control firmware.
- Deye F25DC feedback fault in the bus-voltage sensing circuit.
- Deye F27DC insulation fault reported by the second detection path.
- Deye F28DC overcurrent on MPPT input 1.
- Deye F30AC main contactor or relay fault.
- Deye F31AC slave contactor or relay fault.
- Deye F32DC overcurrent on MPPT input 2.
- Deye F33Grid AC overcurrent.
- Deye F39Internal AC overcurrent (single cycle).
- Deye F40Internal DC overcurrent.
- Deye F45Grid voltage above the configured high-voltage limit.
- Deye F49DC component in the U-phase grid current is too high.
- Deye F50DC component in the V-phase grid current is too high.
- Deye F51Battery temperature reported by the BMS is too high.
- Deye F52DC bus voltage too high (on SG04LP3/SG05LP1 this is reported as F55).
- Deye F53DC bus voltage too low (on SG04LP3/SG05LP1 this is reported as F56).
- Deye F54Battery 2 terminal voltage too high.
- Deye F57Battery 2 terminal voltage too low.
- Deye F60Generator fault.
- Deye F61Inverter manual off: the on/off switch or command is off.
Hybrid inverters (F-series fault codes)2 codes
SUN-5-12K-SG01HP3-EU-DM2 three-phase hybrid (warning codes)11 codes
- Deye W02Internal fan warning: fan operation is abnormal.
- Deye W03Grid phase-sequence warning.
- Deye W04Meter communication failure.
- Deye W05CT direction is wrong.
- Deye W06CT not connected.
- Deye W07External fan 1 warning.
- Deye W08External fan 2 warning.
- Deye W09External fan 3 warning.
- Deye W10Volt-watt activation: grid voltage is high and the inverter is limiting its output.
- Deye W31Battery communication warning: BMS data is abnormal or unstable.
- Deye W32Parallel communication is unstable.
Before you reset a Deye fault
- 1Write down the exact code and any letter before it, and check which Deye model is showing it. The same number can mean different faults on an inverter and on a battery.
- 2Isolate the AC and DC sides before touching terminals, then run the checks on the code's page in order.
- 3If the code comes straight back after a reset, stop resetting it. A repeating fault points to a real wiring, battery or hardware problem.